High power battery capacity test system.
Discharging current up to 1300A with external loads (up to 9).
Graphical display showing test parameters, curves and results.
Internal memory.
Light and easy to carry, with handles and wheels.
Shunt or clamp metering of an additional current.
Suitable for all battery types.
HARDWARE
Maximum number of paralleling test sets 10: 1 master, 9 slave
Absolute maximum battery voltage 270 V
Minimum battery voltage 18 V
Maximum power that can be discharged (one module) 16 kW
Maximum power that can be discharged (10 modules) 160 kW
Max discharging current from 24 V DC to 120 V DC (one
module)
130A
Max discharging current from 24V DC to 120 V DC (ten
modules)
1300A
Max discharging current from 220 V DC to 240 V DC (one
module)
70 A
Max discharging current from 220 V DC to 240 V DC (ten
modules)
700 A
Discharging modes: constant current; constant power;
current profile; manual adjustment
4
Discharging power resolution 100 W
Nominal battery ranges 24, 48, 110, 240 V DC
Battery range setting Automatic, on 4 ranges, as test starts
24 V range limits 20 to 34 V DC
48 V range limits 34 to 60 V DC
72 V range limits 60 to 84 V DC
110/120 V range limits 84 to 140 V DC
240 V range limits 140 to 270 V DC
Maximum starting voltages on the 24 V range 20 to 35 V DC
Maximum starting voltages on the 48 V range 34 to 65 V DC
Maximum starting voltages on the 72 V range 58 to 97 V DC
Maximum starting voltages on the 110 V range 84 to 140 V DC
Maximum starting voltages on the 240 V range 169 to 270 V DC
Battery voltage measurement resolution ± 0.1 V DC
Battery voltage measurement accuracy ± 1% of the maximum range = 2.7 V
Battery current measurement resolution (direct and clip-on
CT)
1 A
Battery current measurement accuracy ± 1% of the maximum range = 1.3 A,
starting from 15 A
V and I measurements refresh period 15 s
Time measurement resolution 1 s
External clip-on CT conversion factor range (programmable) 1 to 500 mV. NOTE: the 1 mV range
is to be used for currents greater than
400 A.
External shunt voltage input 1 to 60 mV
External clip-on CT or shunt accuracy ± 2%
Audible end of test alarm buzzer 5 tones
Alarm output contact 1 SPDT
Display type Graphic 128 x 64 points
Disp
Model: BTS 200 Battery Test System
Accessories:
Power supply cable and earth cable.
No. 2 battery cables, terminated with crocodile clamps.
Software for BTS 200 MKII.
USB interface cable.
Operating Manual.