Our Products

Product Details

 
This testing and maintaining battery system allows to perform measurement of battery voltage, 
discharging current test and testing of battery capacity. BTS 200 can be connected with external load unit ELU 200.
High power battery capacity test system.
Discharging current up to 1300A with external loads (up to 9).
Graphical display showing test parameters, curves and results.
Internal memory.
Light and easy to carry, with handles and wheels.
Shunt or clamp metering of an additional current.
Suitable for all battery types.
HARDWARE
 
Maximum number of paralleling test sets                                  10: 1 master, 9 slave
Absolute maximum battery voltage                                            270 V
Minimum battery voltage                                                            18 V
Maximum power that can be discharged (one module)             16 kW
Maximum power that can be discharged (10 modules)             160 kW
Max discharging current from 24 V DC to 120 V DC (one
module)
                                                                                                   130A
Max discharging current from 24V DC to 120 V DC (ten
modules)
                                                                                                    1300A
Max discharging current from 220 V DC to 240 V DC (one
module)
                                                                                                     70 A
Max discharging current from 220 V DC to 240 V DC (ten
modules)
                                                                                                     700 A
Discharging modes: constant current; constant power;
current profile; manual adjustment
                                                                                                     4
Discharging power resolution                                                      100 W
Nominal battery ranges                                                                24, 48, 110, 240 V DC
Battery range setting                                                                    Automatic, on 4 ranges, as test starts
24 V range limits                                                                           20 to 34 V DC
48 V range limits                                                                           34 to 60 V DC
72 V range limits                                                                           60 to 84 V DC
110/120 V range limits                                                                  84 to 140 V DC
240 V range limits                                                                         140 to 270 V DC
Maximum starting voltages on the 24 V range                               20 to 35 V DC
Maximum starting voltages on the 48 V range                               34 to 65 V DC
Maximum starting voltages on the 72 V range                               58 to 97 V DC
Maximum starting voltages on the 110 V range                             84 to 140 V DC
Maximum starting voltages on the 240 V range                            169 to 270 V DC
Battery voltage measurement resolution                                        ± 0.1 V DC
Battery voltage measurement accuracy ± 1% of the maximum range = 2.7 V
Battery current measurement resolution (direct and clip-on
CT)
                                                                                                            1 A
Battery current measurement accuracy ± 1% of the maximum range = 1.3 A,
starting from 15 A
V and I measurements refresh period                                                 15 s
Time measurement resolution                                                             1 s
External clip-on CT conversion factor range (programmable)             1 to 500 mV. NOTE: the 1 mV range
is to be used for currents greater than
                                                                                                             400 A.
External shunt voltage input                                                                1 to 60 mV
External clip-on CT or shunt accuracy                                                ± 2%
Audible end of test alarm buzzer                                                         5 tones
Alarm output contact                                                                            1 SPDT
Display type Graphic                                                                            128 x 64 points
Disp

Model: BTS 200 Battery Test System

Accessories:

Power supply cable and earth cable.
No. 2 battery cables, terminated with crocodile clamps.
Software for BTS 200 MKII.
USB interface cable.
Operating Manual.