Our Products

Product Details

Partial Discharge Testing & Monitoring -FALCON™ Medium voltage PD monitoring

FALCONTM is representing the latest state of the art technology for partial discharge monitoring (PDM) of MV assets, combining proven and patented technology from HV asset monitoring with economic requirements. FALCONTM is acquiring and processing high frequency PD signals locally detected by the sensors to which it is connected, whether inductive (HFCT), capacitive (TEV).

Industry Segments:

- TRANSMISSION & DISTRIBUTION
- PROCESS INDUSTRIES
- OIL & GAS
- MARINE & TRANSPORTATION
- RENEWABLES
- POWER GENERATION
- OEMS

 

- Economical solution for continuous monitoring of partial discharge in Medium Voltage equipment
- Novel approach to the continuous monitoring of the PD
- Automatic acquisition and elaboration of PD data
- Patented T/F-map technology
- Efficient separation of different discharge activities

TECHNICALL SPECIFICATIONS:

Partial Discharge

PD channel quantity 

Bandwidth 

Sampling frequency at full bandwidth

Resolution 

Sensitivity

Full Scale

Imput impedance

Pre-trigger 

Connector type

Channel quantity 

Frequency range

Imput impedance 

1

16 kHz, 30 MHz

125 MS/s

 12 bit

1,10000 mVpeak 

 5 V peak

50 Ω 

0,100% @ 100 μs

BNC

1

0,1 Hz, 1kHz

10 MΩ

Synchronization input

Sampling frequency at full bandwidth

Resolution

Connector type

1MS/s

12 bit

BNC

Communicationsystem

Ethernet connector

type 

OPCUA 

10/100/1000 Mb/s

2 LAN Ports

IEC 62541

Communication protocol

IEC 61850

Modbus

DNP3

 
Power supply 12 / 24 VDC  
Working temperature -20°C ÷ +55°C  

 

Application:RMU,   MV   Switchgears,   MV   Cables   and   Motors• Using  proven  technology  from  HV  (patented  T/F  Map  technology, Web Application, etc.)
• Compact   and   fully   standalone   unit   with   onboard   computing power and data storage
• Ultra-wide bandwidth acquisition system
• Built in trend analysis with alarm warning based on T-F map• Web browser interface
• Remotely and locally configurable
• OPC-UA IEC 62541 built in protocol
• Easy installation and commissioning
• Automatic  configuration  (Auto-setting)  or  individual settings
• Daisy chainable (LAN and Power)
• Traffic  light  alarm  response  considering  Qmax  and trending