Product overview: Fluke 1507 Insulation Resistance Tester
The Fluke 1507 is a versatile, compact, handheld insulation tester for advanced industrial and electrical insulation testing. Its multiple test voltages make it the ideal tool for many troubleshooting, commissioning, and preventative maintenance applications.
Take advantage of the 1507 full feature set to easily and quickly perform advanced insulation resistance testing. Its handy size and light weight make it easy to pack and use. Additional features, like the remote probe, save both time and money especially when performing repetitive tests. And its reasonable price and rugged reliability make it an excellent value
Key features
Rugged, compact advanced insulation resistance tester for electrical contractors and industrial and commercial electricians
Automatically calculates Polarization Index and Dielectric Absorption Ratio
Makes repetitive tests simple and easy with a Compare (Pass/Fail) function
Offers multiple insulation test voltages: 50 V, 100 V, 250 V, 500 V, and 1000 V
Specifications: Fluke 1507 Insulation
Resistance Tester |
||
AC/DC Voltage Measurement |
|
|
Accuracy |
Range |
600.0 V |
|
Resolution |
0.1 V |
|
50 Hz to 400 Hz ± (% of Rdg + Digits) |
±(2% + 3) |
Input impedance |
3 MΩ (nominal), < 100 pF |
|
Common mode rejection ratio (1 kΩ
unbalanced): |
> 60 dB at DC, 50 or 60 Hz |
|
Overload protection |
600 V rms or DC |
Earth Bond Resistance Measurement |
||
Range/Resolution |
20.00 Ω |
0.01 Ω |
|
200.0 Ω |
0.1 Ω |
|
2000 Ω |
1.0 Ω |
|
20.00 kΩ |
0.01 kΩ |
Accuracy |
±(1.5% + 3) |
|
Overload protection |
2 V rms or DC |
|
Open circuit test voltage |
> 4.0 V, < 8 V |
|
Insulation Specifications |
|
Measurement range |
0.01 MΩ to 10 GΩ |
Test voltage |
50 V, 100 V, 250 V, 500 V, 1000 V |
Test voltage accuracy |
+ 20%, - 0% |
Short circuit current |
1 mA nominal |
Auto discharge |
Discharge time < 0.5 second for C
= 1 µF or less |
Live circuit indicator |
Inhibit test if terminal voltage >
30 V prior to initialization of test |
Maximum capacitive load |
Operable with up to 1 µF loa |
Maximum capacitive load |
Operable with up to 1 µF loa |
|
Measure accuracy |
50 V |
±(3% + 5) |
|
100 V |
±(3% + 5) |
|
250 V |
±(1.5% + 5) |
|
500 V |
±(1.5% + 5) |
|
1000 V |
±(1.5% + 5) to 2000 MΩ, ±(10% + 3)
above 2000 MΩ |
General Specifications |
|
Maximum voltage applied to any
terminal: |
600 V AC rms or DC |
Storage temperature |
-40°C to 60°C (-40°F to 140°F) |
Operating temperature |
-20°C to 55°C (-4°F to 131°F) |
Temperature coefficient |
0.05 x (specified accuracy) per °C
for temperatures < 18°C or > 28°C (< 64°F or > 82°F) |
Relative humidity |
0% to 95% @ 10°C to 30°C (50°F to
86°F) |
|
0% to 75% @ 30°C to 40°C (86°F to
104°F) |
|
0% to 40% @ 40°C to 55°C (104°F to
131°F) |
Vibration |
Random, 2 g, 5-500 Hz per
MIL-PRF-28800F, Class 2 instrument |
Shock |
1 meter drop per IEC 61010-1 2nd
Edition (1 meter drop test, six sides, oak floor) |
Electromagnetic compatibility |
In an RF field of 3 V/M, accuracy =
specified accuracy (EN 61326-1:1997) |
Safety |
Complies with ANSI/ISA 82.02.01
(61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition
for measurement category IV 600 V (CAT IV) |
Models: Fluke 1507 Insulation Resistance Tester
Fluke 1507Fluke 1507 Insulation Resistance Tester
Includes: