Product overview: Fluke 1555 FC 10 kV Insulation Tester
Perform tests, collect data wirelessly and from a safe distance
The Fluke 1555 insulation resistance tester offers digital insulation testing up to 10 kV, making it ideal for testing high voltage equipment including switchgear, motors, generators and cables.
Data collection is easy using the Fluke Connect® wireless app. Remote operation lets you spend as little time as possible in potentially hazardous zones. Real-time trending shows a live graph on your phone, rather than a hard-to-read set of changing values. And you can create reports quickly, using pre-designed templates that you can customize with company logos. The 1555 insulation tester can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating.
Other useful features:
Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
Guard system eliminates the effect of surface leakage current on high-resistance measurements
Selectable test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above 1000 V
CAT III 1000 V, CAT IV 600 V safety rating
Warning function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC for increased user safety
Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
Long battery life gives the user over 750 tests between charges
Large digital/analog LCD for easy viewing
Capacitance and leakage current measurement
Ramp function for breakdown testing
Resistance measurements up to 2 TΩ
Timer settings up to 99 minutes for timed tests
3-year warranty
Key features
Specifications: Fluke 1555 FC 10 kV
Insulation Tester |
|
|
Insulation Resistance Measurement |
|
|
Test voltage (DC) |
|
|
250 V |
Range |
< 250 kΩ,< 250 kΩ, |
|
Accuracy (± reading) |
Unspecified |
500 V |
Range |
< 500 kΩ |
|
Accuracy (± reading) |
Unspecified |
1000 V |
Range |
< 1 MΩ |
|
Accuracy (± reading) |
Unspecified |
2500 V |
Range |
< 2.5 MΩ |
|
Accuracy (± reading) |
Unspecified |
5000 V |
Range |
< 5 MΩ |
|
Accuracy (± reading) |
Unspecified |
10000 V |
Range |
< 10 MΩ |
|
Accuracy (± reading) |
Unspecified |
Bar graph range | 0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555) |
Insulation test voltage accuracy | -0%, +10% at 1 mA load current |
Induced AC mains current rejection | 2 mA maximum |
Charging rate for capacitive load | 5 seconds per μF |
Discharge rate for capacitive load | 1.5 s/μF |
Leakage current measurement |
Range |
1 nA to 2 mA |
|
Accuracy |
±(5% + 2 nA) |
Capacitance measurement |
Range |
0.01 μF to 15.00 μF |
|
Accuracy |
±(15% rdg + 0.03 μF) |
Timer |
Range |
0 to 99 minutes |
Resolution setting |
1 minute |
|
Resolution indication |
1 second |
|
Live circuit warning |
Warning range |
30 V to 660 V AC/DC, 50/60 Hz |
Voltage accuracy |
±(15% + 2 V) |
|
Software specifications |
FlukeView Forms™ basic software
requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8. |
General Specifications |
|
Display |
75 x 105 mm |
Power |
12 V lead-acid rechargeable battery,
Yuasa NP2.8-12 |
Charger Input (AC) |
85 V to 250 V AC 50/60 Hz 20 VA |
Dimensions |
269 x 277 x 160 mm (10.6 x 10.9 x 6.3
in) |
Weight |
3.7 kg (8.2 lb) |
Temperature (operating) |
-20°C to 50°C (-4°F to 122°F) |
Temperature (storage) |
-20°C to 65°C (-4°F to 149°F) |
Humidity |
80% to 31°C decreasing linearly to
50% at 50°C |
Altitude |
2000 m |
Enclosure sealing |
IP40 |
Input overload protection |
1000 V AC |
Electromagnetic compatibility |
EN 61326 |
Safety compliance |
IEC 61010-1: Overvoltage category II,
Pollution Degree 2. |
Models: Fluke 1555 FC 10 kV Insulation Tester
Fluke 1555/KitFluke 1555 10 kV Insulation Tester Kit
Includes: