Key features
Wireless technology allows the display to be carried up to 30 ft. away from the point of measurement with measurement accuracy
Removable magnetic display can be mounted where it is easily seen
iFlex Flexible Current Probe expands the measurement range to 2500 A AC
CAT IV 600 V, CAT III 1000 V
Specifications: Fluke 381 Remote
Display True RMS AC/DC Clamp Meter with iFlex® |
|
Electrical Specifications |
|
AC Current via Jaw |
|
Range |
999.9 A |
Resolution |
0.1 A |
Accuracy |
2% ± 5 digits (10-100 Hz) |
|
5% ± 5 digits (100-500 Hz) |
Crest Factor (50/60 Hz) |
3 @ 500 A |
|
2.5 @ 600 A |
AC Current via Flexible Current Probe |
|
Range |
999.9 A / 2500 A (45 Hz – 500 Hz) |
Resolution |
0.1 A / 1 A |
Accuracy |
3% ± 5 digits |
Crest Factor (50/60 Hz) |
3.0 at 1100 A |
|
2.5 at 1400 A |
|
1.42 at 2500 A |
DC Current |
|
Range |
999.9 A |
Resolution |
0.1 A |
Accuracy |
2% ± 5 digits |
AC Voltage |
|
Range |
600 V /1000 V |
Resolution |
0.1 V / 1 V |
Accuracy |
1.5% ± 5 digits (20 – 500 Hz) |
DC Voltage |
|
Range |
600.0 V /1000 V |
Resolution |
0.1 V / 1 V |
Accuracy |
1% ± 5 digits |
Frequency – Via Jaw |
|
Range |
5.0 – 500.0 Hz |
Resolution |
0.1 Hz |
Accuracy |
0.5% ± 5 digits |
Trigger Level |
5 – 10 Hz, ≥ 10 A |
Frequency via Flexible Current Probe |
|
Range |
5.0 to 500.0 Hz |
Resolution |
0.1 Hz |
Accuracy |
0.5% ± 5 digits |
Trigger Level |
5 to 20 Hz, ≥ 25 A |
Resistance |
|
Range |
600 Ω/6 kΩ/60 kΩ |
Resolution |
0.1 Ω/1 Ω/10 Ω |
Accuracy |
1% ± 5 digits |
Mechanical Specifications |
|
Size (L x W x H) |
277 x 88 x 43 mm (55 mm for remote
unit) |
Weight |
350 g |
Jaw Opening |
34 mm |
Flexible Current Probe Diameter |
7.5 mm |
Flexible Current Probe Cable Length |
1.8 m |
Environmental Specifications |
|
Operating Temperature |
-10°C to +50°C |
Storage Temperature |
-40°C to +60°C |
Operating Humidity |
Non condensing (< 10°C) |
Operating Altitude |
2,000 meters |
Storage Altitude |
12,000 meters |
EMI, RFI, EMC, RF |
EN 61326-1:2006, EN 61326-2-2:2006 |
Temperature Coefficients |
Add 0.1 x specified accuracy for each
degree C above 28°C or below 18°C |
Wireless Frequency |
2.4 GHz ISM Band 10 meter range |
Safety Compliance |
ANSI/ISA S82.02.01:2004 |
|
|
Double Insulation Clearance |
Per IEC 61010-2-032 |
Double Insulation Creepage |
Per IEC 61010-1 |
Models: Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex
Fluke 381Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex
Includes:
18-inch iFlex flexible current probe
Coated instruction card
Safety information sheet
Soft carrying case
TL75 test leads
Five AA Alkaline batteries