The S1-1068 10 kV insulation resistance
tester has been designed, specified and tested to meet the stringent
requirements of power utilities. In addition to being a tough, high performance
insulation tester, the S1-1068 offers the ability to perform accurate
insulation resistance measurements in extreme, high noise environments, rapid
charging of cable capacitance, and even remote operation for both convenience
and safety.
With class-leading noise rejection of 8 mA – twice
that of most comparable instruments – and enhanced software filtering that has
four user-selectable options, Megger’s S1 series of 5 kV, 10 kV, and 15 kV DC
insulation resistance testers deliver dependable results in even the most
severe of electrical environments, including high voltage transmission and
distribution substations.
Other innovative features include provision for
remote control via a fully isolated USB port, which makes the instruments
ideally suited for use in production environments, and internal storage for
date- and time-stamped results. Stored results can be recalled to the display,
downloaded via a Bluetooth wireless link, or accessed via the USB port.
Compact and lightweight, the S1 insulation
resistance testers feature a tough dual-case design and, with the lid closed,
they have an IP65 ingress protection rating. They offer timed insulation
resistance (IR), dielectric absorption ratio (DAR), polarisation index (PI),
dielectric discharge (DD), step voltage (SV) and ramp diagnostic tests, and
also have a dedicated voltmeter function.
To ensure that testing is never delayed through lack
of power, S1 insulation testers incorporate rapid-charge Li-ion batteries.
This gives up to 4.5 hours for the S1-1068. With just 30 minutes of
charging from flat, the batteries give around one hour of testing time, and
it’s also possible to operate the instrument from an AC supply even if the
battery is completely flat.
All S1 models have a
high short-circuit current of 6 mA to ensure rapid charging of item
SPECIFICATIONS
AC
voltage (auto ranging) |
|||||
S1-568,
S1-1068 |
90
– 264 V rms, |
||||
S1-1568 |
90
– 264 V rms, 50/60
Hz, 200 A |
||||
Battery
life |
11.1
V, 5.2Ah meets IEC 62133: 2003
(S1-1568 has 2 batteries) |
||||
Battery
life |
|||||
S1-568:
|
6
hours (typical) continuous testing
at 5 kV with a 100 MΩ load |
||||
S1-1068: |
4.5 hours (typical) continuous testing at 10 kV with a 100 MΩ load |
||||
S1-1568: |
4.5
hours (typical) continuous testing
at 15 kV with a 100 MΩ load |
||||
Auto
power off |
Instrument
turns off after a few minutes if non-use to conserves battery life |
||||
30
min quick charge |
1
hour operation at 5 kV with a 100 MΩ load |
||||
Battery
charge time |
2.5
hours deep discharge, |
||||
Test
voltage |
250
V, 500 V, 1000 V, 2500 V, 5000 |
||||
Lock
test voltage |
40
V to 1 kV in 10 V steps, |
||||
Test
voltage accuracy |
+4%,
-0%, ±10 V nominal test |
||||
Resistance
range |
10
k to 15 TΩ @ 5 kV, |
||||
Accuracy |
|||||
S1-568 |
5000 V |
2500 V |
1000 V |
500 V |
250 V |
±5%
to ±20%
to |
1
TΩ 10
TΩ |
500GΩ 5
TΩ |
200GΩ 2
TΩ |
100GTΩ 1
TΩ |
50
GΩ 500
GΩ |
S1-1068 |
10 kV |
5000 V |
2500 V |
1000 V |
500 V |
±5%
to ±20%
to |
2
TΩ 20
TΩ |
1
TΩ 10
TΩ |
500
GΩ 5
TΩ |
200
GΩ 2
TΩ |
100
GΩ 1
TΩ |
S1-1568 |
15 kV |
10 kV |
5000 V |
2500 V |
1000 V |
±5%
to ±20%
to |
3
TΩ 30
TΩ |
2
TΩ 20
TΩ |
1
TΩ 10
TΩ |
500
GΩ 5
TΩ |
200
GΩ 2
TΩ |