The HVDC test systems are high-performance, portable
test sets that perform DC voltage tests for electrical power supply
components and cables. They are suitable for all kinds of high voltage
DC components in line with the applicable regulations regarding the
generation of HVDC voltages of up to 800 kV. In addition, these units can
also test surge arresters, HVDC transformers or insulators and can perform
leakage measurements.
These effecient HVDC test systems are suitable
for both installation testing in measuring trailers, and on-site testing as a
stationary test set. Their modular structure makes them easy to set up on
site and adaptable to various measuring tasks. Indeed, the spatial
separation of the operating and high-voltage units makes it possible to operate
the sets from outside the immediate danger area.
The sets are primarily designed for power supply
companies, cable laying firms, service providers, cable installers, and
cable manufacturers for the DC voltage testing of high voltage systems and
cables. Their short-circuit-proof output circuit and high power make them
suitable for use in fault location as a burn-down unit for burning
high-impedance and intermittent cable fault.
Key Features
Specification
General:
Residual ripple <
3 % (acc. IEC
60060-1)
Voltage range 0 ... 800 kV, resolution 1 kV
Measuring range ±
3 %
Current range 100 μA... 300 mA (fully-automated range
switchover)
Overcurrent switch off 10
μA ... 100 mA (adjustable)
Test duration 1
Min ... 99 days (adjustable)
Input voltage 220 ... 250 V, 50 / 60 Hz
Operating temperature - 20 °C ... + 55 °C
Storage temperature -
20 °C ... + 70 °C
HVDC 200:
DC output
voltage (**) 0 ... -200 kV
Output current 9
mA @ - 190 kV
Short circuit current IK 50
mA ± 10 %
Max. discharge energy 600 kJ @ 200 kV
Power consumption Pmax kVA (16 A fused)
HVDC 400:
DC output
voltage (**) 0 ...
-400 kV
Output current 4
mA @ - 350 kV
Short circuit current IK 45
mA ± 10 %
Max. discharge energy 600 kJ @ 400 kV
Power consumption Pmax 4 kVA (16 A fused)
HVDC 650:
DC output
voltage (**) 0 ...
-650 kV
Output current 3,5 mA @ - 600 kV
Short circuit current IK 40
mA ± 10 %
Max. discharge energy 1 600 kJ @ 650 kV
Power consumption Pmax 5.5 kVA (25 A fused)
HVDC 800:
DC output voltage (**) 0 ...
-800 kV
Output current 2 mA @ - 800 kV
Short circuit current IK 35
mA ± 10 %
Max. discharge energy 2 000 kJ @ 800 kV
Power consumption Pmax 5.5
kVA (25 A fused)