The T22/1 high voltage test system is a portable test set consisting of two separate units: the control unit and the high voltage unit. This division enables the operator to use the test set on site without transport aids. The test set can be equipped with a rectifier attachment for DC voltage testing up to 80 kV. The light and compact high voltage transformer, insulated with insulating gas (SF 6), produces a high voltage of 75 kVRMS. The voltage is continuously adjustable from 0 to 75 kV using a regulating transformer.
The instrument is primarily used for AC voltage testing low capacity test objects (e.g., metal-enclosed high voltage switchgears), and DC voltage testing cable systems and equipment up to 80 kV using a rectifier attachment.
When using the attachment to generate a DC voltage, the voltage can be measured by using a separate measuring resistor and the M 401 measuring unit.In the basic version for AC voltage testing, the output voltage is calculated and indicated by measuring the primary voltage of the high voltage transformer and converted using the turn factor (M 402 measuring unit). Alternatively, the voltage can be measured on high voltage potential cables by using a measuring resistor and the M 402/1 unit.
Key features
Continuous testing with AC voltages up to 75 kVRMS at 1 kVA
Expandable with a second transformer for testing up to 150 kVRMS
Built-in overload protection
DC testing up to 80 kV with optional rectifier
Compact and light
T 22/1
Power consumption PN 1 kVA
Power consumption 4 kVA
short-time PK (1 min)
Input voltage 230 V / 50 ... 60 Hz
Output voltage 0 ... 75 kVRMS (basic version)
0 ... 150 kVRMS (upgrade version 150 kVRMS)
0 ... 80 kVDC (upgrade version 80 kVDC)
Measuring range 0 ... 80 kVRMS (basic version, multiply by
factor two for upgrade version 150 kVrms) 0 ... 60 kV / 0 ... 120 kVDC
(upgrade version 80 kVDC)
Precision 2.5 %
Output current 0 ... 13 mA
50 mA maximum (1 min)
Measuring range 0 ... 20 ARMS (basic version),
0 ... 200 μA / 0 ... 2 mA / 0 ... 20 mA DC
(upgrade version 80 kVDC)
0 ... 60 mARMS (option current measure- ment HV potential)
Control unit T 22/124
Weight 19 kg
Dimensions (W x H x D) 551 x 255 x 380 mm
Transformer T 22/12
Weight 19kg
Dimensions (ø x H) 420 x 560 mm